SIRCO AC 3X315A F 690Vac

SIRCO AC 3X315A F 690Vac

Model: SIRCO AC 3X315A F 690Vac
Brand: Socomec
Category: Switch Disconnectors & Transfer
Views: 8 views

Products Introduction

Socomec SIRCO AC 3X315A F 690Vac (Order No: 26AC3031) is a reliable switch disconnectors & transfer for industrial power distribution, motor control and UPS systems. Designed for high efficiency and long service life in critical applications. Spec...

  • ProductsDetails
  • Technical Specifications
  • Domestic Alternative

Glorient offers competitive supply of Socomec SIRCO AC 3X315A F 690Vac, Order No: 26AC3031. Competitive pricing, fast quotation.

Socomec SIRCO AC series product. Original SOCOMEC industrial electrical component, model SIRCO AC 3X315A F 690Vac, order number 26AC3031.

More Socomec Products from Glorient

In addition to SIRCO AC 3X315A F 690Vac, Glorient also supplies:

ISOM K-40h Order No: 47250122
FUS gG T0 63A Order No: 67020063
POLE ADDITIONNEL M1 CD 63A Order No: 22001005
EM+ 20KVA 3/3 +L5 Order No: U4EM023M00LE-00
MAS BAT-LL-2x42x40AH-4P-CB Order No: 2MBF42-040L4P-K
ATyS g 3x500A F Order No: 95533050
SHAFT TYPE S-5X5-320MM Order No: 14070532
MAS BAT-LL-2x40x92AH-4M-CB Order No: 2MBF40-092L4M-K
MAS BAT-LL-1x42x92AH-4H-CB Order No: 1MBF42-092L4H
CABLE 6MM2 40A L=320MM BLEU Order No: 54211106
MAS DISBAT-NL-1X40X40AH-4P-CB Order No: 1MBF40D040N4P
SHAFT TYPE S-5X5-200MM Order No: 14070520
SIRCO DC 4X1200A 1000Vdc Order No: 27DC4121
MAS DIS BAT-LL-2X36X9AH-4P-CB Order No: 1MBF72D009L4P
MAS BAT-LL-2x48x25AH-4F-CB Order No: 2MBF48-025L4F-K
CABLE RJ12 3x0.3M Order No: 48290582
TBA100 600/5 cl.0,5 5VA Order No: 192T8060
FUSERBLOC T4 4X1250A F/L Order No: 38116120
ATyS p 3X315A F Order No: 95733031
MAS DIS BAT-NL-2X42X26AH-4P-CB Order No: 2MBF42D026N4P-K
ATyS p 3X1250A F Order No: 95733120
FUSERBLOC CD J 3+NC 30A Order No: 37104004
SIRCOVER BP 3+6P 125A Order No: 41AC7013
MAS BAT-LL-2x40x70AH-2H-CB Order No: 2MBF40-070L2H-K
T2CA225 200/5 cl.0,2s 2,5VA Order No: 192U2220
Height [mm]269
Width [mm]137
Depth [mm]110
Weight [kg]2.01
Control operatorDirect : B2, J1 / External : S2
Number of poles3
Rated voltage690 VAC
Rated current [A]315
TypeFront operation
Frame sizeB4b
GTIN/EAN3596032774431
Customs number8536508000
Price unitPC
Weight of the packing unit [kg]1.941
Length of the packing unit [m]0.235
Width of the packing unit [m]0.11
Depth of the packing unit [m]0.178
DescriptionManually operated Load break switch SIRCO AC frame B4b with 3 poles, 315A, 690 VAC frontal direct operation with handle type J1 or frontal external operation with handle type S2. Delivered without handle
Effective date2012-07-03
Offer Life Cycle Code40
Country of originFR
Conformity to standards['IEC']
UNSPSC39122233
ETIM ClassEC000216
IGCC5290
Version as main switch['Yes']
Version as maintenance-/service switch['Yes']
Version as safety switch['Yes']
Version as emergency stop installation['Yes']
Version as reversing switch['No']
Number of switches1
Motor drive optional['No']
Motor drive integrated['No']
Voltage release optional['No']
Device construction['Built-in device fixed built-in technique']
Type of control element['Other']
Interlockable['Yes']
Type of electrical connection of main circuit['Bolt connection']
Max. rated operation voltage Ue AC [V]690
Rated operating voltage [V]400..690
Rated permanent current Iu [A]315
Rated permanent current at AC-23, 400 V [A]315
Rated permanent current at AC-21, 400 V [A]315
Rated short-time withstand current lcw [kA]8
Rated operation power at AC-23, 400 V [kW]160
Switching power at 400 V [kW]160
Conditioned rated short-circuit current Iq [kA]50
Suitable for floor mounting['No']
Suitable for front mounting 4-hole['No']
Suitable for front mounting centre['No']
Suitable for distribution board installation['No']
Suitable for intermediate mounting['Yes']
Colour control element['Other']
Degree of protection (IP), front side['IP20']
Climate change - Total - Cradle to Grave [kg CO₂ eq.]168
Climate change - Total - Cradle to Gate [kg CO₂ eq.]12
SVHC > 0.1 mass percentage?['No']